TCM-3300

TCM-3300 Detectomat
Intelligent Input module for the connection of one conventional detector zone to the Loop
3000 with bidirectional isolator according to EN 54-18. For the connection of conventional
detectors with 12 V or 24 V technology.

  • Voltage selection for the detector zone supply via „jumper“ on the module board
  • External supply of conventional detector zones for the flexible use of different conventional detectors with different current consumptions and operation voltages
  • Possibility for parametrization of short-circuit, wire break, prealarm and alarm thresholds
  • Automatic and manual addressing with Loop 3000
  • Integrated Isolator and T-branch option
  • Functions completely integrated via Loop 3000-protocol
  • Multicolour LED for alarm (red) and fault (yellow)
  • Aestethical robust wall mounted housing according with IP 54

Technical Data
  • Supply Voltage 15 V bis 32 V DC (abs. max. 34 V DC) auf 2-Drahtbus
  • Quiescent Current 560 μA
  • Alarm Current 560 μA; 5 mA with activated alarm-LED
  • Protection class IP 54
  • Ambient temperature -10°C to +60°C
  • Humidity max. 95%
  • Dimensions (H x B x T) 93 mm x 93 mm x 55 mm
  • Weight appr. 190 g
  • Material ABS, Glass
  • Colour Light grey (similar to RAL 7035)
  • Standards DIN EN 54-18, EN 54-17
  • VDS-approval G 206048
  • CE-CPD-Number 0786-CPD-20373
  • CE-CPR-Number 0786-CPR-20373
  • Brand: DETECTOMAT
  • Product Code: 30205
  • Availability: In Stock
Conventional zone module