The TUN-6046 programmable, microprocessor-based, addressable heat detectors is designed to identify fire hazards in rooms where a rapid temperature rise may occur in the first phase of the fire or the temperature may exceed a certain dangerous level. The detector can be programmed from the control panel. Depending from chosen temperature class detector can operate as fixed, rate-of-rise and fixed/rate-of-rise heat detector. It is also possible to change the detector class, adapting it to specific applications. According to the EN 54-5 standard it is possible to choose from A1, A2, B, A2S, BS, A1R, A2R or BR classes.
Type: addressable, point. Category: Regular working conditions. Variety: heat. Operational voltage: 16,5 VDC - 24,6 VDC. Quiescent current consumption: <150΅A. Detector class: A1, A2, B, A2S, BS, A1R, A2R, BR acc. to PN-EN 54-5. Addressing: Automatic address encoding from the control panel. Operating temperature range: -25°C to 65°C. Relative humidity: up to 95 % at 40°C. Dimensions of detector with base: Φ115 x 54mm. Weight: 0,2kg. Frame colour: white/any colour of the RAL palette (special order only).