Control panel with 1 loop. Loop capability 64 points. Capacity for 8 relays per loop. Allows A50xxLD detectors with visual and sound alarm notification. Search for loop points in sequential order according to their physical position on the cable. Programming of 16 zones. Registry with capacity of 6601 events. Relay configuration with activation of 1, 2 or 3 alarm detectors. Relay trigger auto-configuration function. 2 independent programmable sounder outputs. 2 auxiliary 30V output connectors with programmable reset. Alarm output as an unmonitored voltage-free relay. Fault output, delayed and monitored. Allows addressable acoustic and visual sounders to be connected to the loop. Evacuation push button. Backlit LCD display with 4 lines and 40 characters. It incorporates several languages by default (Spanish, English, French, Portuguese, etc.). Configurable via PC software, I-Link. Access to the panel keypad using a numeric code. Cofem 360 functionality on demand. Dimensions: 363 x 331 x 96 mm (with cover). UL/EU certification according to Standard EN 54 Part 2 and EN 54 Part 4, and CE marking according to European C
Input voltage 110/230 Vac 50/60Hz Maximum current per loop 250mA/24Vdc Output voltage 24V nominal Max. consumption 70VA at 230 VAC Environmental conditions -10?C+50?C 20%-95%RH Communications port USB 2.0/1.1 type B and RS485 Battery charger Yes Devices per loop 64 Dimensions 368x336x96mm (with cover) Weight (without batteries) 4,5kg Standard EN 54 part 2 and 4 IP protection IP30 Battery fuse 4A Output fuse 30V 0,5A Sounder fuse S1 0,75A Sounder fuse S2 0,5A